Rotary Table Zero-Point Guide

1 min read

Applicable Models: VHA, VHL, VHG5


1. Purpose #

Clarify the zero-point reference and proximity-sensor logic for forward and reverse rotation of rotary tables.
This document prevents confusion during service and function testing.


2. Applicable Models #

TypeControllerRepresentative ModelsRotation Method
AIMC400VHA, VHLServo Rotation
BIMC700 / IMC710VHG5Servo Rotation

3. Zero-Point Reference #

ModelZero-Point PositionController Logic Reference
VHA / VHL (IMC400)Reverse-rotation completion positionSet ZRO (0°) at reverse-rotation completion
VHG5 (IMC700/710)Forward-rotation completion positionSet ZRO (0°) at forward-rotation completion

4. Proximity Sensor Logic #

ItemVHA/VHL (IMC400)VHG5 (IMC700/710)Remarks
Forward rotation complete sensorSignal ON (1) = completeSignal OFF (0) = completeLogic inverted
Reverse rotation complete sensorSignal ON (1) = completeSignal OFF (0) = completeLogic inverted
During rotation (intermediate)Both sensors = OFFBoth sensors = ONSignal inversion
Reference directionReverse-rotation completionForward-rotation completionController difference

5. Checklist for Functional Test #

Inspection ItemVHA/VHL (IMC400)VHG5 (IMC700/710)Evaluation Criteria
Forward/Reverse operationNormal rotation in both directionsSameVerify signal at completion
Proximity sensor operationSensor ON at completionSensor ON during rotationCheck sensor status
Zero-point confirmationReverse-rotation completion positionForward-rotation completion positionDisplay = 0°
Position restore after restartNormalNormalZero maintained after power re-apply

6. Service Notes #

  1. Model Identification
    • IMC400 and IMC700/710 use different rotation logic. Confirm controller version first.
  2. Sensor Reuse Caution
    • For logic-inverted models (VHG5), set sensor ON/OFF input as reversed.
  3. Software Parameter
    • Do not change the Zero reference within the standard control logic.
  4. If Zero Mismatch Occurs During Test
    • Check sensor input (IO monitor) → rotation direction → controller version in order.

7. Summary #

  • VHA/VHL (IMC400): Zero = Reverse-rotation complete, Sensor = Completion state
  • VHG5 (IMC700/710): Zero = Forward-rotation complete, Sensor = During rotation
    → Because the logic is inverted, confirm the model-specific reference before all function tests and service operations.